| Your are here : Home| Environmental Standards|Common HW incinerators | Guidelines for common Hazardous Waste Incineration | Annexure - I |
 |
 |
| Emission Standards for Common Hazardous Waste Incineration |
|
 |
| Annexure- I |
| Flue Gas Emission Standards |
Treated flue gas emissions discharge through stack to atmosphere shall always be less than or equal to the following parameter-specific emission standards: |
| Preamble |
| Parameter |
Emission standard |
| Particulates |
50 mg/Nm3 |
Standard refers to half hourly average value |
| HCl |
50 mg/Nm3 |
Standard refers to half hourly average value |
| SO2 |
200 mg/Nm3 |
Standard refers to half hourly average value |
| CO |
100 mg/Nm3 |
Standard refers to half hourly average value |
| 50 mg/Nm3 |
Standard refers to daily average value |
| Total Organic Carbon |
20 mg/Nm3 |
Standard refers to half hourly average value |
| HF |
4 mg/Nm3 |
Standard refers to half hourly average value |
| NOx (NO and NO2 expressed as NO2 ) |
400 mg/Nm3 |
Standard refers to half hourly average value |
| Total dioxins and furans |
0.1 ng TEQ/Nm3 |
Standard refers to 6-8 hours sampling. Please refer guidelines for 17 concerned congeners for toxic equivalence values to arrive at total toxic equivalence. |
| Cd + Th + their compounds |
0.05 mg/Nm3 |
Standard refers to sampling time anywhere between 30 minutes and 8 hours. |
| Hg and its compounds |
0.05 mg/Nm3 |
Standard refers to sampling time anywhere between 30 minutes and 8 hours. |
| Sb + As + Pb + Cr + Co + Cu + Mn + Ni + V + their compounds |
0.5 mg/Nm3 |
Standard refers to sampling time anywhere between 30 minutes and 8 hours. |
|
 |
| Note: All values corrected to 11% oxygen on a dry basis. |
| Operating Standards |
- All the facilities shall be designed to achieve a minimum temperature of 1100°C in secondary combustion chamber and with a gas residence time in secondary combustion chamber not less than 2 (two) seconds.
- The incineration facilities after initial operation of minimum one year, as per the guidelines and standards, can submit a proposal for relaxation in temperature and retention time requirement if it can be demonstrated that the flue gas standards and operation standards can be complied with at lower temperatures and residence times. The State Pollution Control Board / Pollution Control Committee, upon successful demonstration of compliance with flue gas standards by the facility, can recommend the proposal made by the incineration facility for relaxation in temperature and residence time, but in any case not less than 950 °C and 1.5 seconds, for the consideration and approval of the Central Board.
- Incineration plants shall be operated (combustion chambers) with such temperature, retention time and turbulence, so as to achieve Total Organic Carbon (TOC) content in the slag and bottom ashes less than 3%, or their loss on ignition is less than 5% of the dry weight of the material.
- Guidelines published by the Central Board from time to time for common incineration facilities shall be referred for implementation.
- All the project proposals submitted for establishment of the common incineration facilities shall be examined and cleared by the Task Force constituted by the Central Board.
- Notification of compliance: The operator of the incinerator shall undertake comprehensive performance test. Within 90 days of completion of comprehensive performance test, the operator shall issue a notification of compliance documenting compliance or non-compliance, as the case may be, for public information / notice.
|
|
|